AWACS™ Applications Detector Sensitivity Settings
110 NFS-3030 Programming Manual P/N 51345:C 11/4/03
Note: * Signifies the factory default setting.
Appendix Table D-2 Detector Sensitivity Settings
Detector Type Alarm (FlashScan) Pre-Alarm
Photo Electric
SMOKE (PHOTO)
(See note
a
)
AL:1=0.50 %
AL:2=0.73 %
AL:3=0.96 %
AL:4=1.19 %
AL:5=1.43 %
AL:6=1.66 %
AL:7=1.89 %
AL:8=2.12 %*
AL:9=2.35 %
PA:1= Aut o
PA:2= 0.30 %
PA:3= 0.47 %
PA:4= 0.64 %
PA:5= 0.81 %
PA:6= 0.99 %
PA:7= 1.16 %
PA:8= 1.33 %*
PA:9= 1.50 %
Ion
SMOKE (ION)
(See notes
a
and
b
)
AL:1=0.50 %
AL:2=0.75 %
AL:3=1.00 %
AL:4=1.25 %
AL:5=1.50 %
AL:6=1.75 %*
AL:7=2.00 %
AL:8=2.25 %
AL:9=2.50 %
PA:1= Aut o
PA:2= 0.40 %
PA:3= 0.50 %
PA:4= 0.75 %
PA:5= 1.00 %
PA:6= 1.25 %*
PA:7= 1.50 %
PA:8= 1.75 %
PA:9= 2.00 %
FlashScan View
(See Note
b
)
AL:1=0.03 %
AL:2=0.05 %
AL:3=0.10 %
AL:4=0.20 %
AL:5=0.30 %
AL:6=0.50 %*
AL:7=0.70 %
AL:8=0.80 %
AL:9=1.00 %
PA:1= Aut o
PA:2= 0.02 %
PA:3= 0.03 %
PA:4= 0.05 %
PA:5= 0.10 %
PA:6= 0.20 %*
PA:7= 0.30 %
PA:8= 0.40 %
PA:9= 0.50 %
Acclimate
Multi-Sensor
AL:1=0.50 %
AL:2=1.00 %
AL:3=1.00 to 2.00 %
AL:4=2.00 %
AL:5=2.00 to 3.00%*
AL:6=3.00 %
AL:7=3.00 to 4.00 %
AL:8=4.00 %
AL:9=thermal 135
o
F
Alarm (CLIP)
AL:1=1.00 %
AL:2=1.00 %
AL:3=1.00 to 2.00 %
AL:4=2.00 %
AL:5=2.00 to 4.00%*
AL:6=2.00 to 4.00%
AL:7=2.00 to 4.00%
AL:8=4.00 %
AL:9=4.00%
PA:1= 0.50 %
PA:2= 1.00 %
PA:3= 1.00 %
PA:4=1.00 to 2.00%
PA:5=1.00 to 2.00 %*
PA:6= 2.00 %
PA:7= 2.00 %
PA:8=2.00 to 3.00 %
PA:9=2.00 to 3.00 %
Heat (Adjustable Threshold) AL:1=43
°
C
AL:2=57
°
C
AL:3=63
°
C*
AL:4=68
°
C
AL:5=74
°
C
AL:6=88
°
C
AL:7=88
°
C
AL:8=88
°
C
AL:9=88
°
C
PA:1= 40
°
C
PA:2= 43
°
C
PA:3= 57
°
C*
PA:4= 65
°
C
PA:5= 70
°
C
PA:6= 75
°
C
PA:7= 75
°
C
PA:8= 75
°
C
PA:9= 75
°
C
* Signifies the factory default setting.
a. Suitable for open area protection only with 0 to 300 feet per minute air velocity.
b. The use of alarm sensitivities below 0.50% obscuration per foot requires a 90 day test to ensure that the environment for
the detectors is suitable for the higher sensitivity setting. (Refer to “How to Test Detectors Set Below 0.50% Obscuration
per Foot” on page 111.)
www.PDF-Zoo.com