Alter Status Disable/Enable
62 NFS-3030 Programming Manual P/N 51345:C 11/4/03
4.2 Disable/Enable
A point can be disabled or enabled using this screen. Press the DISABLE/ENABLE soft key at the
Alter Status screen to display the following.
Figure 4.3 Disable/Enable Screen
Soft Keys
DISABLE/ENABLE Only the applicable command will display. Press to disable an installed,
programmed point, or to enable a disabled one.
WARNING:Do not rely on Disable to disable releasing points during testing. Releasing points
must be physically disconnected.
4.3 Detector Sensitivity
This screen is displayed when the “Detector Sensitivity” soft key is pressed on the Alter Status
Menu screen.
Figure 4.4 Sensitivity Select Point Screen
Soft Keys
POINT: Press to place the cursor in the format field. Type the address using the keyboard.
NEXT/PREVIOUS SELECTION: Press these soft keys to scroll sequentially through the detector
addresses on the loop. The screen will display the next loop when the last device on this loop is
passed.
ACCEPT: Press to proceed to the Detector Sensitivity screen.
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A FRI JUL 19, 2002
DISABLE/ENABLE: L03D052
AUTOMATIC INACTIVE
ELEVATOR LOBBY EAST WING
FIFTH FLOOR Z005 SMOKE(PHOTO)
VALUES: 011% OF ALARM, 045% OF PREALARM
DISABLE BACK
!
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A FRI JAN 21, 2002
POINT SELECT
POINT: LyyDzzz (DETECTOR)
NEXT SELECTION ACCEPT
PREVIOUS SELECTION BACK
www.PDF-Zoo.com