Point Program Program
NFS-3030 Programming Manual P/N 51345:C 11/4/03 39
full description and a table of the nine sensitivity levels by detector type.
Soft Keys
OCCUPIED SENSITIVITY ALARM:
OCCUPIED SENSITIVITY PREALARM:
UNOCCUPIED SENSITIVITY ALARM:
UNOCCUPIED SENSITIVITY PREALARM:
ALARM SENSITIVITY TABLE: This table will toggle from ALARM to PREALARM based on
which sensitivity value is being entered. The table will display the values for this type of detector.
Detector Occupancy Schedule
Figure 3.28 Detector Occupancy Schedule Screen
Soft Keys
WEEKLY OCCUPANCY SCHEDULE: Press this soft key to place the cursor at the underlined
field. There can be up to ten Weekly Occupancy Schedules. Enter a value of zero through ten. Zero
indicates no schedule is applied, and occupied detector sensitivity values are used.
ACCEPT: Press this key to accept the change made and return to the previous screen.
Press the soft key next to
these setting categories to
enter values as described
above.
DETECTOR OCCUPANCY SCHEDULE
WEEKLY OCCUPANCY SCHEDULE: 10
SUNDAY - -
MONDAY 08:00-12:00, 13:00-18:00
TUESDAY 08:00-12:00, 13:00-18:00
WEDNESDAY 08:00-12:00, 13:00-18:00
THURSDAY 08:00-12:00, 13:00-18:00
FRIDAY 08:00-12:00, 13:00-18:00
SATURDAY 08:00-12:00, -
HOLIDAY UNOCCUPIED
ACCEPT
BACK
www.PDF-Zoo.com