NFS-3030 Programming Manual P/N 51345:C 11/4/03 23
AUTO SILENCE: Press to enter a value of OFF (no Auto Silence Timer), or a value of 10, 15 or 20
minutes. This global software timer functions like pressing the SIGNAL SILENCE key. For
example, if a value of 10 is entered, the control panel will silence all active outputs programmed as
silenceable after ten minutes. Default: 0FF
Note: This value must be 20 minutes for ULC installations.
VERIFY=PREALARM: Press this soft key to enter Yes or No for displaying Prealarm during alarm
verification. Default: NO
3.2.5 Panel Timers (Menu 2)
Press the MORE soft key on the Panel Timers Menu 1 screen to display the following screen.
Figure 3.8 Panel Timers (Menu 2) Screen
Soft Keys
PAS: Press to toggle between the choices of OFF or ON for PAS (Positive Alarm Sequence). Refer
to Appendix C: Special Zone Outputs for an explanation of this option. Default: OFF
PRESIGNAL DELAY: Press to enter a value of 00:00 (OFF) or a value of 1:00 to 3:00 minutes (in
the format MM:SS, where MM= minutes, SS=seconds). This feature initially causes alarm signals
to sound only in specific areas, monitored by qualified personnel. This allows delay of the alarm for
up to 3 minutes after the start of alarm processing. Refer to Appendix C: Special Zone Outputs for
further explanation of this option. Default: 3:00
DEFAULT TIMERS: Press this soft key to activate default settings for the following:
ACCEPT: Press this soft key to save the information entered on this screen and return to the
previous screen.
3.2.6 LCD Programming
The LCD Programming screen allows the user to vary the contrast of the display and turn the
Program setting for: Default:
Verify Time 30 seconds
Max. Verify 20
AC Fail Delay 8 hours
SIlence Inhibit 0 (disabled)
Auto Silence Off
Verify=Prealarm No
PAS OFF
Presignal Delay 3 minutes
PANEL TIMERS
PAS: OFF
PRESIGNAL DELAY: MM:SS
DEFAULT TIMERS
ACCEPT
BACK