Program Panel Program
20 NFS-3030 Programming Manual P/N 51345:C 11/4/03
DISPLAY ADDRESS: Press this soft key to toggle between Yes and No. Choose Yes to display all
point address information at the top of event screens and in printouts. Choose No to suppress
address information display and printing. Default: Yes
REMINDER MENU: Press this soft key to bring up the Reminder Menu screen.
ACCEPT: Press this soft key to save the information entered on this screen.
MORE: Press this key to progress to the second Panel Settings screen.
Figure 3.5 Panel Settings (2) Screen
Soft Keys
LCM LOCAL MODE: Press this soft key to toggle between Yes and No. Enter Yes to enable all SLCs
to participate in local mode. When enabled, the LCM will operate in a limited fashion when
communication is lost with the NFS-3030/E CPU. Inputs on the LCM loop (and associated LEM
loop, if installed) will activate outputs on the same loop(s)
• when the inputs and outputs have been set with point programming to participate in local mode
• when the type codes are of the same type: that is, an input with a fire alarm type code will
activate an output with a fire alarm type code
Default: NO
PANEL CIRCUIT BELL CODING: Press to toggle between MARCH and TEMPORAL. This is a
global setting: ZF8 must be entered in the zone map of any panel circuit point that will participate
in this coding. Refer to “Coding Functions for Panel Circuit Outputs” on page 104 for more
information. Default: MARCH
DCC PARTICIPATION: Press this key to program the panel for DCC (Display and Control Center)
participation. This network function ensures that one location at a time is in command of the
Acknowledge, System Reset, Signal Silence and Drill functions. Default: NO
CAUTION: On systems utilizing the DCC function, all locations that can participate in DCC
should be set to YES.
DEFAULT SETTINGS: Press this soft key to activate default settings for the following:
Program setting for: Default:
Local Control Yes
Piezo On
Proprietary Supervising Station No
Event Ordering USA
Display Address Yes
LCM Local Mode No
Panel Circuit Bell Coding March
DCC Participation No
PANEL SETTINGS
LCM LOCAL MODE: YES
PANEL CIRCUIT BELL CODING: MARCH
DCC PARTICIPATION: NO