Program Autoprogram Menu
58 NFS-3030 Programming Manual P/N 51345:C 11/4/03
NO: Press to leave the point information in the panel’s database.
Figure 3.51 Autoprogram Confirmation Screen (Mismatched Point)
Display
The
OLD field contains the information currently in the panel’s programming database. The NEW
field contains the information found during autoprogramming. The fields contain the FlashScan
Type ID codes if the device is FlashScan, or they will contain the device type if CLIP.
Soft Keys
YES: Press this soft key to accept the new device type.
EDIT: This soft key will appear only when SLC devices are mismatched. It will not appear for
panel modules. Press it to advance to the point programming screen for this point.
NO: Press if the new information should not be installed over the existing information in the
database.
Figure 3.52 Autoprogram Confirmation Screen (Double Address)
Display
The SLC loop number and device address are displayed where the Autoprogram has found more
AUTOPROGRAM CONFIRMATION
MISMATCHED MODULE FOUND AT PXX
OLD:CONTROL-ICM
NEW:CONTROL-CRM
ACCEPT CHANGES?
YES NO
BACK
EDIT will appear here when the
mismatched point is an SLC device
AUTOPROGRAM CONFIRMATION
DOUBLE ADDRESS FOUND AT LXXDXXX
ACCEPT
BACK
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier NFS-3030/E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-3030/E and is the answer not in the manual?

Notifier NFS-3030/E Specifications

General IconGeneral
BrandNotifier
ModelNFS-3030/E
CategoryControl Panel
LanguageEnglish

Related product manuals