4-3 Wiring Conforming to EMC Directives
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
  4
System Design
Surge Absorber
 Use surge absorbers to absorb lightning surge voltage and abnormal voltage from power supply
input lines.
 When selecting surge absorbers, take into account the varistor voltage, the surge immunity and
the energy tolerated dose.
 For 200-VAC systems, use surge absorbers with a varistor voltage of 620 V.
 The surge absorbers shown in the following table are recommended.
Note 1. Refer to the manufacturers' catalog for operating details. 
Note 2. The surge immunity is for a standard impulse current of 8/20 μs. If pulses are wide, either 
decrease the current or change to a larger-capacity surge absorber.
External Dimensions
Equalizing Circuits
Manufacturer
Model Surge immunity Type Comment
Okaya Electric 
Industries Co., 
Ltd.
RAV-781BWZ-4
700 V ± 20% 2500 A
Block
Single-phase 
100/200 VAC
Okaya Electric 
Industries Co., 
Ltd.
RAV-781BXZ-4
700 V ± 20% 2500 A
3-phase 200 VAC
123
28
4.5
28.5 11
5.5
φ
4.2
41
200
For 3-phase (BXZ series)