5-19
5-4 Internally Set Speed Control
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
   5
BASIC CONTROL Mode
5-4 Internally Set Speed Control
Outline of Operation
 Performs motor speed control using the speeds set in the No. 1 to 8 Internally Speed Settings.
 Select the internally set speed using Internally Set Speed Selections 1 to 3 of the control input
terminals (VSEL1: CN-1 to 33 pins, VSEL2: CN-1 to 30 pins, VSEL3: CN-1 to 28 pins).
Parameters Requiring Settings
Parameter 
number
Parameter name Explanation Reference
Pn001
CONTROL mode 
Selection
Select the CONTROL mode for internally set speed 
control. (Set values: 1, 3 and 5)
P.8-2
Pn300
Command Speed 
Selection
Select the speed command input method.
P.8-26
Pn304 No. 1 Internally Set Speed Set the internally set speeds (r/min).
The settings can be made from -20,000 to 20,000 r/min. Be 
sure to set the speeds within the allowable range of 
rotation speed of the motor.
P.8-27
Pn305 No. 2 Internally Set Speed
Pn306 No. 3 Internally Set Speed
Pn307 No. 4 Internally Set Speed
Pn308 No. 5 Internally Set Speed
Pn309 No. 6 Internally Set Speed
Pn310 No. 7 Internally Set Speed
Pn311 No. 8 Internally Set Speed