6-5 Encoder Dividing Function
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Applied Functions
6-5 Encoder Dividing Function
Outline of Operation
The number of output pulses from the driver can be adjusted.
You can set the number of pulses per motor rotation in the range of 1 to (the number of encoder
resolution pulses).
This function is used in the following cases:
- When you use a controller with a low response frequency
- When you want to set the pulse rate corresponding to a certain value
Example: Set the encoder dividing ratio to 2,000 (pulses/rotation) for when the
resolution is set to 5 μm/pulse on mechanical systems that travel 10 mm per
motor rotation.
Parameters Requiring Settings
Parameter
number
Parameter name Explanation Reference
Pn011
Encoder Dividing
Numerator
Set the number of phase-A and phase-B output
pulses, respectively per motor rotation.
P.8-7
Pn012
Encoder Output
Direction Switching
Selection
Select the phase B logic for pulse regeneration
output and the output source. P.8-7
Pn503
Encoder Dividing
Denominator
Set the denominator when the number of pulses
per motor rotation in pulse regeneration is not an
integer.
P.8-46
Pn533
Pulse Regeneration
Output Limit Setting
Set whether to enable or disable the detection of
Err28.0 "pulse regeneration error."
0: Disabled, 1: Enabled
P.8-58
Pn620
External Scale Phase-
Z Setting
Set the external scale phase-Z output width.
P.8-61
Pn621
Serial Absolute External
Scale Phase-Z Setting
Set the phase-Z regeneration position when the
serial absolute external scale is used.
0: Phase-Z output only at a position where the
absolute position is 0
1 to 2
28
: After a phase-Z output at the position
where the absolute position is 0, phase Z
is output every the set value pulse cycle.
No phase-Z is output until passing absolute
position 0
P.8-61
Pn622
Phase AB External
Scale Pulse Output
Method Selection
Select the regeneration method of pulse outputs
OA and OB when an external scale of phase AB-
output type is used.
0: Without signal regeneration. Z-out is directly Z-
in in the scale
1: With signal regeneration
P.8-62