6-6 Brake Interlock
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
6
Applied Functions
Servo ON/OFF Operation Timings <When Motor Is Rotating>
Based on these operation timings, regenerative energy is produced if the motor rotation stops
abnormally.
Accordingly, repeated operations cannot be performed. Provide a wait time of at least 10
minutes for the motor to cool down.
*1. The servo will not turn ON until the motor rotation speed drops to approx. 30 r/min or below.
*2. The dynamic brake operation when the servo is OFF depends on Stop Selection with Servo OFF (Pn506).
*3. The brake interlock (BKIR) signal is output upon a release request from servo control. The BKIR signal is allocated
to a CN1 general-purpose output to be used.
In the above example, no release request is received from the network.
*4. t1 is the set value of Brake Timing during Operation (Pn438), or the time needed for the motor rotation speed to
drop to 30 r/min or below, whichever occurs first.
Note:Even when the servo ON input is turned ON again while the motor is decelerating, the system will not enter the
servo ON state until the motor stops.