8-24
8-3 Vibration Suppression Parameters
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
8
Parameters Details
Set vibration frequency 3 to suppress vibration at the end of the load in damping control.
Measure the frequency of vibration at the end of the load and make the setting in units of 0.1 Hz.
Setting frequency is 1.0 to 200.0 Hz. The function will be disabled if the setting is 0 to 0.9 Hz.
Refer to "6-1 Anti-vibration Control" (P.6-3) for more information on settings.
First set the Vibration Frequency 3 (Pn218). Then reduce the setting if torque saturation occurs or
increase the setting to increase operation speed. Normally, use a setting of 0.
Set value is restricted in the following manner.
Upper limit: Corresponding vibration frequency
Lower limit: Vibration frequency + vibration filter setting 100
Refer to "6-1 Anti-vibration Control" (P.6-3) for more information on settings.
Set vibration frequency 4 to suppress vibration at the end of the load in damping control.
Measure the frequency of vibration at the end of the load and make the setting in units of 0.1 Hz.
Setting frequency is 1.0 to 200.0 Hz. The function will be disabled if the setting is 0 to 0.9 Hz.
Refer to "6-1 Anti-vibration Control" (P.6-3) for more information on settings.
First set the Vibration Frequency 4 (Pn220). Then reduce the setting if torque saturation occurs or
increase the setting to increase operation speed. Normally, use a setting of 0.
Set value is restricted in the following manner.
Upper limit: Corresponding vibration frequency
Lower limit: Vibration frequency + vibration filter setting 100
Refer to "6-1 Anti-vibration Control" (P.6-3) for more information on settings.
The position command filter time constant is the first-order lag filter inserted after the electronic
gear ratio for the command pulse input.
The position command filter time constant can be used for the following:
· If the command pulses change abruptly, the filter can be used to reduce the stepping
movement of the motor.
· The following are examples of when the command pulses can change abruptly:
The electronic gear ratio setting is high (10 times or higher).
The command pulse frequency is low.
Pn218
Vibration Frequency 3
Setting
range
0 to 2,000 Unit 0.1 Hz
Default
setting
0
Power OFF
and ON
Position
Pn219
Vibration Filter 3 Setting
Setting
range
0 to 1,000 Unit 0.1 Hz
Default
setting
0
Power OFF
and ON
Position
Pn220
Vibration Frequency 4
Setting
range
0 to 2,000 Unit 0.1 Hz
Default
setting
0
Power OFF
and ON
Position
Pn221
Vibration Filter 4 Setting
Setting
range
0 to 1,000 Unit 0.1 Hz
Default
setting
0
Power OFF
and ON
Position
Pn222
Position Command Filter Time Constant
Setting
range
0 to 10,000 Unit 0.1 ms
Default
setting
0
Power OFF
and ON
Position
Full closing