8-4 Analog Control Parameters
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
8
Parameters Details
Explanation of Set Values
Explanation of Set Values
Set the allowable difference (feedback pulse error) between the motor (encoder) position and load
(external scale) position in command units.
The feedback pulse error is reset every time the motor rotates for the amount set by the Internal/
External Feedback Pulse Error Counter Reset (Pn329). This can be used for purposes where
feedback pulse error accumulates due to slippage.
When using feedback pulse error reset, make sure the feedback pulse error reset setting is set to
a proper value. In the case of an extremely small value, it may not function as a protection against
error operations caused by erroneous connection of external scale.
Take sufficient care to ensure safety.
Set
value
Explanation
0 External scale feedback pulse count direction non-reverse
1 External scale feedback pulse count direction reverse
Pn327
External Feedback Pulse Phase-Z Setting
Setting
range
0 to 1 Unit −
Default
setting
0
Power OFF
and ON
Yes
Full closing
Set
value
Explanation
0 Phase-Z disconnection detection enabled
1 Phase-Z disconnection detection disabled
Pn328
Internal/External Feedback Pulse Error Counter Overflow Level
Setting
range
1 to 2
27
Unit Command unit
Default
setting
16000
Power OFF
and ON
Yes
Full closing
Pn329
Internal/External Feedback Pulse Error Counter Reset
Setting
range
0 to 100 Unit Rotation
Default
setting
0
Power OFF
and ON
Yes
Full closing
Feedback pulse
error value [command unit]
(absolute value)
Excessive
feedback pulse
error setting
Occurrence of excessive
feedback pulse
deviation error
Motor rotation
speed [rotation]
Feedback pulse error reset setting