420
Auxiliary Area Section 9-11
Pulse Output 1 Out-
put Completed Flag
A28103 ON when the number of output pulses set with
the PULS(886)/PLS2(887) instruction has been
output through pulse output 1.
0: Output not completed.
1: Output completed.
Read only Cleared when
power is turned
ON.
Cleared when
operation starts or
stops.
Refreshed at the
start or comple-
tion of pulse out-
put in
independent
mode.
Pulse Output 1 Out-
put In-progress Flag
A28104 ON when pulses are being output from pulse
output 1.
0: Stopped
1: Outputting pulses.
Read only Cleared when
power is turned
ON.
Cleared when
operation starts or
stops.
Refreshed when
pulse output
starts or stops.
Pulse Output 1 No-
origin Flag
A28105 ON when the origin has not been determined for
pulse output 1 and goes OFF when the origin
has been determined.
0: Origin established.
1: Origin not established.
Read only Turned ON when
power is turned
ON.
Turned ON when
operation starts.
Refreshed when
pulse output
starts or stops.
Refreshed each
cycle during the
overseeing pro-
cesses.
Pulse Output 1 At-
origin Flag
A28106 ON when the pulse output PV matches the ori-
gin (0).
0: Not stopped at origin.
1: Stopped at origin.
Read only Cleared when
power is turned
ON.
Refreshed each
cycle during the
overseeing pro-
cesses.
Pulse Output 1 Out-
put Stopped Error
Flag
A28107 ON when an error occurred while outputting
pulses in the pulse output 1 origin search func-
tion.
The Pulse Output 1 Output Stop Error code will
be written to A445.
0: No error
1: Stop error occurred.
Read only Cleared when
power is turned
ON.
Refreshed when
origin search
starts.
Refreshed when a
pulse output stop
error occurs.
PWM(891) Output 0
Output In-progress
Flag
A28300 ON when pulses are being output from
PWM(891) output 0.
0: Stopped
1: Outputting pulses.
Read only Cleared when
power is turned
ON.
Cleared when
operation starts or
stops.
Refreshed when
pulse output
starts or stops.
PWM(891) Output 1
Output In-progress
Flag
A28308 ON when pulses are being output from
PWM(891) output 1.
0: Stopped
1: Outputting pulses.
Read only
Name Address Description Read/Write Times when data is
accessed

Table of Contents

Related product manuals