420
Auxiliary Area Section 9-11
Pulse Output 1 Out-
put Completed Flag 
A28103 ON when the number of output pulses set with 
the PULS(886)/PLS2(887) instruction has been 
output through pulse output 1.
0: Output not completed.
1: Output completed.
Read only • Cleared when 
power is turned 
ON.
• Cleared when 
operation starts or 
stops.
• Refreshed at the 
start or comple-
tion of pulse out-
put in 
independent 
mode.
Pulse Output 1 Out-
put In-progress Flag
A28104 ON when pulses are being output from pulse 
output 1.
0: Stopped
1: Outputting pulses.
Read only • Cleared when 
power is turned 
ON.
• Cleared when 
operation starts or 
stops.
• Refreshed when 
pulse output 
starts or stops.
Pulse Output 1 No-
origin Flag
A28105 ON when the origin has not been determined for 
pulse output 1 and goes OFF when the origin 
has been determined.
0: Origin established.
1: Origin not established.
Read only • Turned ON when 
power is turned 
ON.
• Turned ON when 
operation starts.
• Refreshed when 
pulse output 
starts or stops.
• Refreshed each 
cycle during the 
overseeing pro-
cesses.
Pulse Output 1 At-
origin Flag
A28106 ON when the pulse output PV matches the ori-
gin (0).
0: Not stopped at origin.
1: Stopped at origin.
Read only • Cleared when 
power is turned 
ON.
• Refreshed each 
cycle during the 
overseeing pro-
cesses.
Pulse Output 1 Out-
put Stopped Error 
Flag
A28107 ON when an error occurred while outputting 
pulses in the pulse output 1 origin search func-
tion. 
The Pulse Output 1 Output Stop Error code will 
be written to A445.
0: No error
1: Stop error occurred.
Read only • Cleared when 
power is turned 
ON.
• Refreshed when 
origin search 
starts.
• Refreshed when a 
pulse output stop 
error occurs.
PWM(891) Output 0 
Output In-progress 
Flag
A28300 ON when pulses are being output from 
PWM(891) output 0.
0: Stopped
1: Outputting pulses.
Read only • Cleared when 
power is turned 
ON.
• Cleared when 
operation starts or 
stops.
• Refreshed when 
pulse output 
starts or stops.
PWM(891) Output 1 
Output In-progress 
Flag
A28308 ON when pulses are being output from 
PWM(891) output 1.
0: Stopped
1: Outputting pulses.
Read only
Name Address Description Read/Write Times when data is 