554
Specifications of Basic I/O Units Appendix A
Terminal Connections
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate if
polarity is reversed.
• Be sure to wire both terminals A9 and B9 (COM (0 V)) of CN1.
• Be sure to wire both terminals A10 and B10 (+V) of CN1.
• Be sure to wire both terminals A9 and B9 (COM) of CN2, and set the same polarity for both pins.
0
2
4
6
8
10
12
14
16
18
0204060
(°C)
Number of Simultaneously ON Points vs.
Ambient Temperature Characteristic
16 points at 33°C 16 points at 45°C
Number of simultaneously ON points
Input voltage: 24 V DC
Input voltage: 26.4 V DC
12 points at 55°C
9 points at 55°C