384
Host Link Commands Section 6-3
Parameters Name, Word address, Bit (Command)
In “Name,” specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be
forced reset. Specify the name in four characters. In “Word address,” specify
the address of the word, and in “Bit” the number of the bit that is to be forced
reset.
Note The area specified under “Name” must be in four characters. Add spaces after
the data area name if it is shorter than four characters.
6-3-26 MULTIPLE FORCED SET/RESET –– FK
Force sets, force resets, or cancels the status of the bits in one word in the IR,
SR, LR, HR, AR, or TC area.
Command Format
Response Format An end code of 00 indicates normal completion.
Parameters Name, Word address (Command)
In “Name,” specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be
forced set or reset. Specify the name in four characters. In “Word address,”
specify the address of the word that is to be forced set or reset.
Name Classification Word address setting range Bit
OP1 OP2 OP3 OP4 CQM1 PCs CPM1/CPM1A/
SRM1 PCs
C I O (Space) IR or SR 0000 to 0252 0000 to 0019
0200 to 0252
00 to 15
(decimal)
L R (Space) (Space) LR 0000 to 0063 0000 to 0015
H R (Space) (Space) HR 0000 to 0099 0000 to 0019
A R (Space) (Space) AR 0000 to 0027 0000 to 0015
T I M (Space) Completion Flag (timer) 0000 to 0511 0000 to 0127 Always 00
T I M H Completion Flag (high-speed timer)
C N T (Space) Completion Flag (counter)
C N T R Completion Flag (reversible counter)
*
@ FKx 10
0
x 10
1
x 10
3
x 10
2
x 10
1
x 10
0
OP1 OP2 OP3 OP4
↵
15 14 13 12 11 10 1 0
Node no. Header
code
Name Word
address
Forced set/reset/cancel data
Bit
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
TerminatorFCS
@ FKx 10
0
x 10
1
x 16
1
x 16
0
↵
Node no. Header
code
TerminatorFCSEnd code