384
Host Link Commands Section 6-3
Parameters Name, Word address, Bit (Command)
In “Name,” specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be
forced reset. Specify the name in four characters. In “Word address,” specify
the address of the word, and in “Bit” the number of the bit that is to be forced
reset.
Note The area specified under “Name” must be in four characters. Add spaces after
the data area name if it is shorter than four characters.
6-3-26 MULTIPLE FORCED SET/RESET –– FK
Force sets, force resets, or cancels the status of the bits in one word in the IR,
SR, LR, HR, AR, or TC area.
Command Format
Response Format An end code of 00 indicates normal completion.
Parameters Name, Word address (Command)
In “Name,” specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be
forced set or reset. Specify the name in four characters. In “Word address,
specify the address of the word that is to be forced set or reset.
Name Classification Word address setting range Bit
OP1 OP2 OP3 OP4 CQM1 PCs CPM1/CPM1A/
SRM1 PCs
C I O (Space) IR or SR 0000 to 0252 0000 to 0019
0200 to 0252
00 to 15
(decimal)
L R (Space) (Space) LR 0000 to 0063 0000 to 0015
H R (Space) (Space) HR 0000 to 0099 0000 to 0019
A R (Space) (Space) AR 0000 to 0027 0000 to 0015
T I M (Space) Completion Flag (timer) 0000 to 0511 0000 to 0127 Always 00
T I M H Completion Flag (high-speed timer)
C N T (Space) Completion Flag (counter)
C N T R Completion Flag (reversible counter)
*
@ FKx 10
0
x 10
1
x 10
3
x 10
2
x 10
1
x 10
0
OP1 OP2 OP3 OP4
15 14 13 12 11 10 1 0
Node no. Header
code
Name Word
address
Forced set/reset/cancel data
Bit
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
TerminatorFCS
@ FKx 10
0
x 10
1
x 16
1
x 16
0
Node no. Header
code
TerminatorFCSEnd code

Table of Contents

Other manuals for Omron CPM1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CPM1 and is the answer not in the manual?

Omron CPM1 Specifications

General IconGeneral
ModelCPM1
ManufacturerOmron
Instruction SetBasic and advanced instructions
Power Supply100 to 240 VAC or 24 VDC
CommunicationRS-232C
I/O Points10, 20, 30, or 40 points depending on the model
TimersYes, multiple timers available
CountersYes, multiple counters available
Input Voltage24V DC
Output TypeRelay or transistor
Number of I/O Points10, 20, 30, 40
Communication PortsRS-232C (optional)
Operating Temperature0°C to 55°C
Storage Temperature-20°C
Humidity10% to 90% (non-condensing)
DimensionsVaries depending on the model
WeightVaries depending on the model
Program Memory2048 steps (2K steps)

Related product manuals