108
Functionality for All Option Board's Section 7-1
Safety Output Terminal Data Flags
The flags show the ON/OFF values monitored for Safety Output terminals.
0: Output terminal OFF.1: Output terminal ON.
Safety Input Terminal Status Flags
These flags are the normal status flags for self-diagnosis of the Safety Input
terminals. They are used to monitor for Safety Input terminal errors, such as
disconnected lines, ground fault, and short-circuit.
0: Error.1: Normal operation (no error).
Safety Output Terminal Status Flags
These flags are the normal status flags for self-diagnosis of the Safety Output
terminals. They are used to monitor for Safety Output terminal errors, such as
disconnected lines, ground fault, and short-circuit.
0: Error.1: Normal operation (no error).
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 So 07 So 06 So 05 So 04 So 03 So 02 So 01 So 00
+1 So 15 So 14 So 13 So 12 So 11 So 10 So 09 So 08
+2 Reserved
+3 Reserved
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Si 07 Si 06 Si 05 Si 04 Si 03 Si 02 Si 01 Si 00
+1 Si 15 Si 14 Si 13 Si 12 Si 11 Si 10 Si 09 Si 08
+2 Reserved Si 19 Si 18 Si 17 Si 16
+3 Reserved
+4 Reserved
+5 Reserved
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 So 07 So 06 So 05 So 04 So 03 So 02 So 01 So 00
+1 So 15 So 14 So 13 So 12 So 11 So 10 So 09 So 08
+2 Reserved
+3 Reserved