Functionality for All Option Board's Section 7-1
Unit Status
These flags indicate the overall status of the G9SP-series Controller.
Configuration ID
Unit Conduction Time
This is the total time that the G9SP-series Controller has been ON and oper-
ating normally. The Unit Conduction Time is updated and saved every six min-
utes. The time is given in minutes.
For example, if the G9SP-series Controller has been ON for 100 days, 12
hours, and 12 minutes, 100 x 24 x 60 + 12 x 60 + 12 = 144,732 (minutes) =
02355C hex (minutes). This data is stored as follows:
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Unit Nor-
mal Operat-
ing Flag
+1 Reserved Reserved Function
Block Error
Flag
Reserved Reserved Safety I/O
Ter mi na l
Error Flag
Output
Power Sup-
ply Error
Flag
Reserved
Status name Meaning
Unit Normal Operating Flag 0: Error occurred or program stopped.
1: Normal status (no error) and program being executed.
Output Power Supply Error Flag 0: Output power supply voltage normal.
1: Output power supply voltage error or power supply OFF.
Safety I/O Terminal Error Flag 0: No error in Safety I/O terminals.
1: Error in Safety I/O terminals.
Function Block Error Flag 0: No error in any function block.
1: Error in a function block.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Configuration ID rightmost byte
+1 Configuration ID leftmost byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Unit Conduction Time, first byte (rightmost byte)
+1 Unit Conduction Time, second byte
+2 Unit Conduction Time, third byte (leftmost byte)
+3 Reserved
+0 5C
+1 35
+2 02
+3 00 (reserved)