111
Functionality for All Option Board's Section 7-1
Present Error Information
The details of errors occurring in the G9SP-series Controller are displayed
using a bit maps. Multiple bits turn ON if multiple errors have occurred. Refer
to subsequent pages for error details and corresponding bit maps.
Error Log Count
This is the number of errors registered in the error log (0 to 10). Refer to 10-1-
3 Error Log for information on the error log count.
Operation Log Count
This is the number of operations registered in the log (0 to 10). Refer to 10-1-
4 Operation Log for information on the operation log count.
Error Log
This is a log of recorded errors. The error details are given using the following
error codes. The Unit Conduction Time is also stored when an error occurs.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Error Information Map 0
+1 Error Information Map 1
--- ---
+11 Error Information Map 11
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Error Log Count
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Operation Log Count
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Error record 1 (most recent) error code
+1 Error record 1 (most recent) Unit Conduction Time third byte at error
+2 Error record 1 (most recent) Unit Conduction Time second byte at error
+3 Error record 1 (most recent) Unit Conduction Time first byte at error
--- ---
+36 Error record 10 (oldest) error code
+37 Error record 10 (oldest) Unit Conduction Time third byte at error
+38 Error record 10 (oldest) Unit Conduction Time second byte at error
+39 Error record 10 (oldest) Unit Conduction Time first byte at error