18
G9SP-series Controllers Section 2-1
• ON pulse width when semiconductor output is OFF: 30 µs max.
Test Output Specifications
*1 Connection to an OMRON D40A or D40Z Non-Contact Switch is possi-
ble.
*2 With the Muting Lamp Output (open circuit detection)
Safety Output Specifications
*1 Total current for So0 to So3 and So4 to So7.
*2 Total current for So0 to So3, So4 to So7, So8 to So11, and So12 to So15.
Precautions for Safe Use
When a Safety Output is set as a pulse output, make sure that the connected
device does not malfunction for the OFF pulse (pulse width: 640 µs).
700 µs max.
30 µs max.
Item Specification
Output type Sourcing outputs (PNP)
Rated output current G9SP-N10S T0, T1: 60 mA max.
T2: 30 mA max.
*1
T3: 300 mA max.
*2
T0-2 total: 60mA max.
G9SP-N10D T0, T1, T2: 60 mA max.
T3: 300 mA max.
*2
T4, T5: 30 mA max.
*1
T0-2, T4-5 total: 60mA max.
G9SP-N20S T0, T1, T2: 100 mA max.
T3: 300 mA max.
*2
T4, T5: 30 mA max.
*1
T0-2, T4-5 total: 120 mA max.
ON residual voltage 1.8 V max. (between test outputs and V1)
Leakage current 0.1 mA max.
Item Specification
Output type Sourcing outputs (PNP)
Rated output current 0.8 A max./point
1.6 A max./4 points (N10S or N20S)
*1
1.2 A max./4 points (N10D)
*2
ON residual voltage 1.2 V max. (between outputs and V2)
OFF residual voltage 2 V max.
Leakage current 0.1 mA max.