EasyManua.ls Logo

Panasonic 2WAY Multi - P18 Bypass Valve Error

Panasonic 2WAY Multi
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IV–94
P18 Bypass Valve Error
Error detection method
A warning is output if it is determined that the outdoor unit needs a bypass valve inspection.
In practical terms, what happens is that each time there is a small difference ( P 0.1 MPa) between the
high and low pressure ( P = high pressure - low pressure) 90 seconds after stopping the engine stops, a
suspected error counter increments, and the data is recorded as “pre-trip” warning history data. After the
counter reaches 5, a warning is output on the next complete combustion startup.
Understanding the warning history
The latest P18 data in the warning history is issued immediately after a complete combustion startup. It is not
the data used for detecting the error. If a pre-trip error was detected (when the suspected error counter reaches 5),
that data is the next more recent P18 data.
Troubleshooting
1
Bypass
valve
inspection
1-1
Bypass valve inspection
During operation, use the No. 4 test mode “v_close” (close
valve) to close the bypass valve (step 0). Check whether
refrigerant is not leaking on entering the bypass.
OK 1-2
NG
Replace the bypass
valve unit
1-2
Bypass valve inspection
After completing the above inspections, stop the engine and
use No.4 test mode “v_open” (open valve) to open the bypass
to check that the bypass valve operates normally despite the
uctuations in tube temperature around the bypass valve.
OK 2-1
NG 1-3
1-3
Outdoor main board inspection
Is there approximately 12 V of pressure at bypass valve output
ports 5 (+) and 1 to 4 (-) when the power is on?
Yes 1-4
No
Replace outdoor main
board
1-4
Electric valve coil inspection
Are the resistance values for electric valve connectors 5 and
1 to 4 about 40 Ω?
Yes
Replace the bypass
valve unit
No
Replace the bypass
valve coil
2
Four-way
valve
Inspect
outdoor
solenoid
valves
2-1 Is the outdoor unit a 3-WAY MULTI-device?
Yes 2-3
No 2-2
2-2 Is the four-way valve free from leakage?
OK 3-1
NG
Replace the four-way
valve
2-3
Are the outdoor solenoid valves (discharge valves 1 and 2,
and suction valves 1 and 2) free from leakage?
* Suction valve 1 closes when current ows through it (other
solenoid valve remain open)
OK 3-1
NG
Replace the solenoid
valve.
3
Liquid valve
inspection
3-1
Liquid valve inspection
Any refrigerant leaks past the liquid valve when the liquid
valve is completely closed (step 0)?
OK 4-1
NG
Replace the liquid valve
unit
4
Expansion
valve
inspection
4-1
Is the operation mode heating?
* Note: If you are operating with a 3WAY MULTI, try 4-2 and
4-3 before shutting down the engine as this might be
due to cooling and heating mixed operation.
Yes 4 -2
No 4-3
4-2
Outdoor expansion valve inspection
Check that there are no refrigerant leaks past the outdoor
expansion valve when the engine is stopped in heating mode.
OK 5-1
NG
Replace the outdoor
expansion valve unit
4-3
Indoor electric valve inspection
Stop the indoor unit during cooling operation (multiple indoor
unit operation, indoor electric valve opening = 20 steps) and
check to make sure there is no coolant leakage beyond the
indoor electric valve.
OK 5-1
NG
Replace indoor electric
valve unit
5
Pressure
sensor
inspection
5-1
Pressure sensor inspection (refer to the section on F16 for the
inspection procedure)
OK
Replace outdoor main
board
NG Repair
For work procedure for replacing outdoor main board, see “5. Reference Document.
GHPtroubleshooting.indbIV‒94GHPtroubleshooting.indbIV‒94 2012/11/2611:20:142012/11/2611:20:14

Table of Contents

Related product manuals