L05·06 Duplicate Indoor Unit Priority Setting
(Cannot be detected when the water heat exchanger unit is connected.)
Error detection method
An error is determined when multiple indoor units have the operation mode priority setting within the same
refrigeration tubing system.
• The indoor unit with the priority setting displays L05.
• The indoor units without the priority setting display L06.
• When multiple units have the operation mode priority setting, set in remote controller simple settings mode.
Troubleshooting
1
Operation
mode
priority
setting
1-1
Check operation mode priority (item code 04) in remote controller simple settings mode, and
assign operation mode priority setting (1) to only one indoor unit.
● See “5. Reference Document” for detailed remote controller settings.