EasyManua.ls Logo

Panasonic 2WAY Multi - P20 Refrigerant High-Pressure Error

Panasonic 2WAY Multi
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IV–96
P20 Refrigerant High-Pressure Error
Error detection method
When the high pressure sensor value 3.75 MPa during engine operation, the engine stops and an error ag
is set. A Refrigerant Pressure Too High fault is assumed when this ag has stopped the engine 5 consecutive
times in 1 hour.
When revolution speed setting is more than minimum revolution speed and fan frequency is less than 50% of
maximum frequency, an error is not generated. (The engine stops momentarily.)
Troubleshooting
1
Cooling/
heating
mode
1-1 Operating in the cooling mode or heating mode?
Cooling 2-1
Heating 3-1
2
Outdoor
units heat
exchanger
check
2-1
Is the heat exchanger clogged by foreign matter or other
debris (visual inspection)?
Yes Remove
No 2-2
2-2 Is there an air shortage?
Yes
Revise
installation
No 2-3
2-3 Is the fan on the outdoor unit operating?
Yes 12-1
No
Refer to section
P22
3
Tubing 3-1
Are there any crushed tubes, torn strainers, closed servicing
valves, or other problems? Check the temperature of the
indoor unit’s coil.
Yes Repair
No 4-1
4
Unit check
4-1
Which is connected, an indoor unit or a water heat exchanger
unit?
Proceed to 5-1 when the
indoor unit is connected
Proceed to 8-1 when the
water heat exchanger unit is
connected
5
Indoor
units heat
exchanger
check
5-1 Is the air lter on the indoor unit clogged?
Yes Clean the lter
No 5-2
5-2 Is the fan on the indoor unit operating?
Yes 6-1
No Repair
6
Indoor unit’s
motor-
operated
valve check
6-1
Check the indoor unit’s motor-operated valve. Does the valve
open? (Check the indoor units heat exchanger temperature
when in the heating mode.)
Yes 7-1
No 6-2
6-2
Check the indoor unit’s control board. (Is there any voltage
between No. 5 (+) and No. 1-4 (-) of the indoor units control
board PMV6P (white) CN082 when the power is switched on?)
Yes 6- 3
No
Replace the
indoor units
control board
6-3
Check the motor-operated valve coil. (Does a resistance of
approximately 46 Ω exist between No. 5 and No. 1-4 of the
motor-operated valve connector 5P (white)* or 6P (white)?)
Yes
Replace the
valve
No
Replace the
valve coil
7
Indoor unit’s
coil sensor
7-1
Are indoor unit’s coil sensors E1, E2, and E3 disconnected
from their measurement points? Check this by displaying the
indoor coil temperature on the outdoor unit.
Yes Repair
No 11-1
8
Cold/hot
water check
8-1
Is a correct cold/hot water (brine) ow volume being
maintained?
Yes
Maintain the
rated ow volume
No 8-2
8-2 Is the cold/hot water (brine) pump operating?
Yes 9-1
No Repair
GHPtroubleshooting.indbIV‒96GHPtroubleshooting.indbIV‒96 2012/11/2611:20:142012/11/2611:20:14

Table of Contents

Related product manuals