EasyManua.ls Logo

Panasonic 2WAY Multi - F30 Real Time Clock (RTC) Function Error

Panasonic 2WAY Multi
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IV–64
F30 Real Time Clock (RTC) Function Error
Error detection method
An error is determined when the standard pulse (every 1 second) from the outdoor main board clock function
(RTC) cannot be read.
Troubleshooting
1
Clock
function
1-1
Turn OFF the outdoor unit, then turn ON and observe. If the error recurs, replace outdoor
main board
For work procedure for replacing outdoor main board, see “5. Reference Document.
For board and Electrical Wiring Diagram, see Chapter 6.
Outdoor main board: page VI-2
Outdoor power board: page VI-3
• Converter board: VI-4
Indoor control board for DC motor models: page VI-5
Outdoor Unit Electrical Wiring Diagram: page VI-6
GHPtroubleshooting.indbIV‒64GHPtroubleshooting.indbIV‒64 2012/11/2611:20:112012/11/2611:20:11

Table of Contents

Related product manuals