EasyManua.ls Logo

Panasonic 2WAY Multi - Checks Prior to Automatic Addressing

Panasonic 2WAY Multi
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V–53
(10) Checks Prior to Automatic Addressing
* When an outdoor unit alarm is displayed, perform the following checks after troubleshooting.
1
Indoor/outdoor power
source
1-1 Indoor and outdoor units turned on?
Yes 2-1
No Turn on the power
2
Indoor/outdoor control
wires
2-1
Have the inside/outside control wires been laid? Is there a
break or disconnection of wires?
Yes 2-2
No
Wiring and
connection
2-2
Was a high voltage (200 V AC), etc. applied to the control
wire circuit?
Has a fuse on the control board blown?
[Con rmation of each outdoor and indoor unit]
Yes 2-3
No 3-1
2-3
There is a problem with the wiring of the power cable and indoor/outdoor control wires.
Turn off the power, check and repair faulty wiring, and then connect all indoor/outdoor
control wires to the backup control board and controller.
3
Outdoor settings 3-1
Does the setting of connected indoor unit count (No. 10)
on the outdoor control board match the actual count of
connected indoor units?
Yes 3-2
No Correct the setting
3-2
Are the indoor/outdoor control wires connected to multiple
outdoor units?
(Wire-linked?)
Yes 3-3
No 3-6
3-3
Is S010 (terminal resistor ON/OFF switch) on the outdoor
main board set to ON for only one outdoor unit and set to OFF
for all other outdoor units *1?
Yes 3-4
No Correct the setting
3-4 Are there any duplicate settings for outdoor units?
Yes 3-5
No 3-6
3-5
For link wiring, set a system address for each outdoor unit in the order of 1, 2, 3, and then
perform automatic addressing.
3-6 Perform automatic addressing.
*1: Terminal resistor is basically “ON(SHORT)” for one unit only, but depending on the installation status can be
set to “ON(SHORT)” for up to 3 units.
•2-3
Backup connectors and terminals for indoor/outdoor control wires (for communication)
Equipment Primary Backup
Outdoor Unit CN045 (for communication) CN046 (EMG)
Indoor unit CN040(0C) CN044(EMG)
System controller Terminal block No. A7 and B7 Terminal plate No. 3 (Indoor/outdoor backup control wire)
Multi-controller Terminal plate No. 2 (U2) Terminal block No. 3
Intelligent controller Terminal block No. 2 Terminal block No. A6 and B6
AMY adapter JP3-A side JP3-B side
* For a system linking wiring systems, if the systems are connected to water heat exchange unit, depending on
the state of the hot / cold water, automatic address alarm may occur.
If this happens, remove the link wiring and set address individually.
GHPtroubleshooting.indbV‒53GHPtroubleshooting.indbV‒53 2012/11/2611:20:252012/11/2611:20:25

Table of Contents

Related product manuals