EasyManua.ls Logo

Panasonic 2WAY Multi - P03 High Compressor Discharge Temperature

Panasonic 2WAY Multi
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IV–82
P03 High Compressor Discharge Temperature
Error detection method
When the compressor discharge temperature 130°C during engine operation (complete combustion), the
engine is stopped and an error ag is set.
A Compressor Discharge Temp. High fault is assumed when this ag has shut down the engine 5 consecutive
times.
Revolution speed setting > minimum revolution speed is not included in pre-trip.
Not included in pre-trip when liquid valve opening 400 step.
Troubleshooting
1
Sensor 1-1
Disconnect compressor outlet temperature sensor connector
2P (red) CN054 and measure resistance. Appropriate value?
(See “5. Reference Document” for thermistor characteristics.)
Yes 2-1
No Replace sensor
2
Out of gas
2-1
Out of gas? Determine using compressor outlet pressure,
compressor inlet pressure, and indoor/outdoor electric valve
opening.
Yes
Repair leak and
charge gas.
No 3-1
3
Tubing
3-1
Any symptoms of pump down? Determine with indoor coil
temperature
Yes
Inspect indoor
unit tubing
No
Inspect outdoor
unit tubing
4
Inspect
outdoor
solenoid
valves (For
three-way
device)
4-1
Adjust outdoor solenoid valves. Use trial operation mode
to check that the solenoid valves operate normally in
each operating mode (cooling/heating) and measure
tube temperature around solenoid valves to assess. (For
information on solenoid valve operation in each operating
mode, see the sections Control functions - Operating control
in the “Outdoor unit manual.” Does the solenoid valve operate
normally?
Yes
Replace outdoor
main board
No 4-2
4-2
Adjust the power board.
Does the power board CN013 output the solenoid power
supply voltage (AC 200V)?
Yes 4 - 3
No
Replace power
board
4-3
Any poor connection and broken wires in wiring between the
power board and the relay board?
Yes Repair wir ing
No 4-4
4-4
Adjust the outdoor main board.
In No. 4 test mode when “v_open” (valve open), is there a
drive output voltage (12 V DC) from discharge valves 1-1, 1-2,
discharge valve 2, suction valve 2-1 and 2-2?
(9P (white) CN018)
Discharge valve 1-1, 1-2: between No. 3 - 9 Discharge valve 2:
between No. 4-9
Suction valve 2-1, 2-2: between No. 6 - 9
Does suction valve 1 output a drive voltage (DC 12V) during
cooling operation?
Suction valve 1: between No. 3 - 9
* Note that suction valve 1 closes when powered (the other
valves operate in the opposite way)
Yes 4 - 5
No
Replace outdoor
main board
4-5
Any poor connection and broken wires in wiring between the
outdoor main board and the relay board?
Repair wiring
4-6
4-6
Adjust the relay board.
In No. 4 test mode when “v_open” (valve open), is there an
output voltage (AC 200V) from discharge valves 1-1, 1-2,
discharge valve 2, suction valve 2-1 and 2-2?
Does suction valve 1 output a voltage (AC 200V) during
cooling operation?
Yes 4 -7
No
Replace relay
board
4-7
Adjust the solenoid valve coil.
(Be sure to turn the power off before starting work.)
Disconnect the connectors of discharge valve 1-1, 1-2,
discharge valve 2, suction valve 1, suction valve 2-1 and 2-2
from the relay board and measure the resistance between No.
1 and 3.
Normal value (20°C) discharge valve 1-1, 1-2: 543 ohm
discharge valve 2: 1132 ohm
Suction valve 1: 1197 ohm suction valve 2-1, 2-2: 543 ohm
Is the coil operating normally?
Resistance
is normal
Replace solenoid
valve
Abnormal
resistance
Replace the
solenoid valve
coil
GHPtroubleshooting.indbIV‒82GHPtroubleshooting.indbIV‒82 2012/11/2611:20:132012/11/2611:20:13

Table of Contents

Related product manuals