IV–72
L08 Indoor Unit Address Not Set
Error detection method
An error is determined when the indoor unit capacity is not set.
• When the indoor unit address was not set when new non-volatile memory (EEPROM) was installed.
• When indoor unit address in the remote controller detailed settings mode is “invalid.”
Troubleshooting
1
Indoor unit
Set address
1-1
Use the remote controller detailed settings mode to check indoor unit addresses (item code
13) and set an indoor unit address to replace invalid (0) ones.
● See “5. Reference Document” for detailed remote controller settings.