IV–47
E11 Indoor Unit Receive Failure from Signal Output Board
(Cannot be detected when the water heat exchanger unit is connected.)
Error detection method
After confi rming existence of the signal output board, an error is determined upon no reception from the signal
output board.
• Signal output board is defective.
• Wiring to signal output board is defective.
Troubleshooting
1
Signal output
board
1-1
Wiring to signal output board (option board) broken or
short-circuited?
Yes Repair wir ing
No 1-2
1-2
Replace the signal output board (option board) and wiring.
Is E11 displayed again?
Yes
Replace indoor control
board
No
Replace signal output
board
● See instructions packaged with servicing indoor board for procedure on replacing indoor control board.
GHPtroubleshooting.indbIV‒47GHPtroubleshooting.indbIV‒47 2012/11/2611:20:102012/11/2611:20:10