IV–48
E12 Automatic Address Setting Is in Progress: Automatic Address Setting Start is Prohibited
(Cannot be detected when the water heat exchanger unit is connected.)
Error detection method
An error is determined when an auto-addressing startup command is received from another unit during auto-
addressing.
In a system with multiple outdoor units, with indoor/outdoor operation wiring connected (with link wiring),
an auto-addressing startup command was issued by another unit during auto-addressing.
Troubleshooting
1
Autoaddress
1-1
In a system with multiple outdoor units, with indoor/outdoor operation wiring connected (with
link wiring), an auto-addressing startup command was issued by another unit during auto-
addressing.
Wait until current auto-addressing is complete.