E24 Communication Failure between Outdoor Units (for only W MULTI)
Error detection method
An Outdoor Communication Unit Failure is assumed when communications between outdoor units in the same
refrigerant system are not possible for 2 minutes.
• An outdoor unit address has not been properly assigned.
• Outdoor unit power is OFF.
Troubleshooting
1
Power
supply,
wiring
1-1
Have outdoor unit addresses and outdoor unit and number of
connected outdoor units been properly entered?
Yes 1-2
No Enter the data correctly.
1-2 Have all outdoor units in the same system been turned on?
Yes 1-3
No Turn power ON
1-3
The indoor/outdoor operation wiring may not be connected between the indoor unit and
outdoor unit.
Check wiring connections on indoor/outdoor operation wiring.