V–26
9) Forced engine distributor mode (Level 2) ... Used when xing ignition timing.
Display :

Rejection conditions : None
Operating method : Press the SET (S007) key for one second while forced engine distributor mode is
not set. (TEST/WARNING LED light)
Operation details : Activates forced engine distributor mode.
Forced setting in progress display (TEST/WARNING LED light) is shown during
this time.
Releasing method : Press the SET (S007) key for one second while in forced engine distributor mode.
The forced setting in progress display will be canceled at this time, returning to
forced setting select operation. (TEST/WARNING LED off)
10) Forced engine feedback (Level 2)
Display :

Rejection conditions : None
Operating method : Press the SET (S007) key for one second while forced engine feedback is not set.
(TEST/WARNING LED light)
Operation details : Activates feedback control.
Forced setting in progress display (TEST/WARNING LED light) is shown during
this time.
Releasing method : Press the SET (S007) key for one second during forced engine feedback.
The forced setting in progress display will be canceled at this time, returning to
forced setting select operation. (TEST/WARNING LED off)
11) Forced engine adjustment valve position (Level 2)
Display :

Rejection conditions : Indoor unit operation in progress.
Operating method : Press the SET (S007) key for one second while the forced engine adjustment valve
closing is not set. (TEST/WARNING LED light)
Operation details : Set fuel gas adjustment valve at full closing position.
Forced setting in progress display (TEST/WARNING LED light) is shown during
this time.
Releasing method : Press the SET (S007) key for one second when forced engine adjustment valve is
being closed.
Forced setting in progress display is canceled (TEST/WARNING LED off)
and forced setting selection operation returns. (After positioning, forced engine
adjustment valve closing position is canceled automatically.)