Network and Power Requirements
ThefollowingnetworkandpowerrequirementsapplytotheEpicinsertingsystem.
Network Requirements
l Dataconcentratorethernethub(min.4-port)
l CAT5cablefromeachDCandRTPPCtodataconcentratorhub
l CAT5cablefromdataconcentratorhubtodataconcentrator(modifiedPIDAserverprovided)
l Internetconnecttodataconcentrator(LAN)
Power Requirements
l Domesticpower(Canada,US,andMexico)
l 3Phase,208VAC,60Hz,50amp4-wireconnection(L1,L2,L3,Earth)
l Powerplugfor3-wireplusearthdomesticconnectionsupplied
l Powerplugsupplied-NEMA15-50P(Hubbell8451Corequivalent)
l Powerreceptaclerequired:NEMA15-50Rreceptacle(Hubbell8450Aorequivalent)
l Export3phase,230VACor240VACphasetoneutral(400VACor415VACphasetophase),
50Hz,50ampsperphase,(L1,L2,L3,N,Earth)
l Powerplugfor5-wireexportconnection
l Powerplugfor5wireconnectionisnotprovided.Asuitablepowerconnectorratedat240/415V,
50Aminimumandinletwiringthatconformstolocalwiringstandardsmustbechosenbythe
customer.(Connections are made by the customer to terminals inside the MPS power inlet
assembly. Wiring diagram shown on inside of removable front cover of the inlet assembly.)
l TypicalcutsheetMPSconfiguration(powered on and processing work)-3phaseapproximate
31Atotal(6.448KVA)
l TypicalcontinuousMPSconfiguration(powered on and processing work)-3phaseapproximate
36Atotal(7.448KVA)