10.2.2 Begin Register Test
Description
Verify on the meter faceplate the current registration value. Enter that value into the “Start
Register” Field. Press F1 “Start” to begin the test.
10.2.3 Register Test Results
Description
Once the test is complete, enter the register value from the meter faceplate again, and the %
error will be calculated versus measured and calculated values.
Rev 1.5 84