EasyManua.ls Logo

Primes PROFINET - Page 69

Primes PROFINET
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PowerMeasuringModule PMM
35,0(6
69
Revision 13 EN - 02/2023
After the integration of the DeviceNet™ scanner and the PMM into the system, the data of the PMM are
displayed in the data range of the scanner first (see Fig. 13.5 on page69):
Fig. 13.5: Data range of the scanner
The entry „Local:2:O.CommandRegister.Run = 1“ in Fig. 13.5 on page69 --> sets the scanner into the
RUN-Mode. Only then data will be transferred from the scanner to the PMM.
The RUN-Mode of the scanner can be checked by means of the status register in Fig. 13.5 on page69
--> „Local:2:I.StatusRegister.Run = 1“.
The two-digit segment display of the scanner bears
the bus address of the scanner. If the bus address is
0, the display will depict “00”.
If run = 0, the bus address and the error code are
displayed alternately. The error codes are listed in the
manual of the scanner by Rockwell.

Table of Contents

Related product manuals