Page 165
The third parameter for each relay determines the assignment or
condition of the relay, where required.
P212, P222, P232, P242, P252 - Relay Alarm ID/Pump Group,
When Ultra Wizard = 2 Pump Differential
P211, 221, 231, 241, 251 = 1, 2, 3 or 6
This parameter has no function and will not be displayed.
P211, 221, 231, 241, 251 = 4 (Flush Valve)
If the relay is selected for Flush Valve/Pump, then this parameter is used to
determine to which pump the Flush function is assigned. Enter the relay
number to which the assigned pump is connected.
P211, 221, 231, 241, 251 = 5 (Step Time)
If the relay is selected for Step Time, then this parameter is used to assign
the relay to the 0 = Open condition (increase level) or 1 = Close condition
(decrease level).
When Ultra Wizard = 3 Flow
P211, 221, 231, 241, 251 = 2 (Step Time)
If the relay is selected for Step Time, then this parameter is used to assign
the relay to the 0 = Open condition (increase level) or 1 = Close condition
(decrease level).