EasyManua.ls Logo

Rievtech PR-6DC-DA-R - Page 373

Rievtech PR-6DC-DA-R
393 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
373
Accuracy at 25 °C
---
± (Max.0.02)V
Accuracy at 55 °C
---
± (Max.0.04)V
Isolation between analog
channel and power supply
---
None
Cable length
---
10 m max. shielded and twisted
Output parameters:
Output No.
4 (Q1-Q4)
4 (Q1-Q4)
Output type
Relay output
Transistor output
Continuous current
Resistive load 10A/Inductive load 2A
0.3A
Max. breaking voltage
AC 250 V /DC 110 V
DC 30V
Max. Allowable Power Force
1250VA /300W
9W
Electrical durability
Expectancy
10
5
Operations at Rated Resistive Load
---
Mechanical life
10
7
Operations at No Load condition
---
Response time
Operate Time : 15 mSec. Max.
Release Time : 10 mSec. Max.
Operate Time : <1 ms
Release Time : <1 ms
Built-in protections
Against short-circuits: None
Against overvoltages and overloads: None
Switch frequency:
Mechanism
10Hz
---
Resistor/light load
2Hz
10HZ
Sensitive load
0.5Hz
0.5HZ
PWM frequency
---
10K HZ(Q3,Q4 must have
same frequency when
PWM works)
PWM accuracy at 500Hz
---
< 0.5% (20 % 80 %)
load at 10 mA
Other parameters:
Function blocks
512 blocks
RTC accuracy :
MAX ±2S/day
RTC Backup at 25 °C
20 days
Program and settings
Backup
10 Years
Data Power-off retentivity
Yes
Weight
Approx.300g
Short-circuit protection
External fuse required
Cycle time
typ. 0.6ms 8.0ms
Connection cables
2 x 1.5 mm² or 1 x 2.5 mm²
Ambient temperature
-20 to + 55 ºC
Storage temperature
–40 ºC to + 70 ºC
Certification
CE
Mounting
On 35 mm standard mounting rail, 4 MW, or wall-mounting
Dimensions
W x H x D (72*90*61 mm)

Table of Contents