375
Isolation between inputs
None
None
Protection against polarity
inversions
Yes
None
Inputs used as analog inputs( I1-I6 )
Measurement range
---
DC 0---10V
Input impedance
---
Min, 24KΩ ; Max. 72KΩ
Input voltage
---
28.8 V DC max
Resolution
---
10bit ,0.01V
Accuracy at 25 °C
---
± (Max.0.02)V
Accuracy at 55 °C
---
± (Max.0.04)V
Isolation between analog
channel and power supply
---
None
Cable length
---
10 m max. shielded and twisted
Output parameters:
Output No.
4 (Q1-Q4)
Output type
Relay output
Continuous current
Resistive load 10A/Inductive load 2A (Relay)
Max. breaking voltage
AC 250 V /DC 110 V(Relay)
Max. Allowable Power Force
1250VA /300W(Relay)
Electrical durability
Expectancy
10
5
Operations at Rated Resistive Load(Relay)
Mechanical life
10
7
Operations at No Load condition(Relay)
Response time
Operate Time : 15 mSec. Max.(Relay)
Release Time : 10 mSec. Max.(Relay)
Built-in protections
Against short-circuits: None
Against overvoltages and overloads: None
Switch frequency:
Mechanism
10Hz
Resistor/light load
2Hz
Sensitive load
0.5Hz
PWM frequency
---
PWM accuracy at 500Hz
---
Other parameters:
Function blocks
512 blocks
RTC accuracy :
MAX ±2S/day
RTC Backup at 25 °C
20 days
Program and settings
Backup
10 Years
Data Power-off retentivity
Yes
Weight
Approx.400g
Short-circuit protection
External fuse required
Cycle time
typ. 0.6ms 8.0ms
Connection cables
2 x 1.5 mm² or 1 x 2.5 mm²