8. PARAMETER DESCRIPTION
IMR02C15-E4
8-110
Dummy
F41
Event 1 hold action
F42
Event 2 hold action
F43
Event 3 hold action
F44
Event 4 hold action
Use to set an event hold action for the Event 1.
Use to set an event hold action for the Event 2.
Use to set an event hold action for the Event 3.
Use to set an event hold action for the Event 4.
Data range Factory set value
0: OFF
1: Hold action ON (Only hold action)
• Validate the hold action when the power is
turned on.
• Validate the hold action when transferred
from STOP (control STOP) to RUN (control
RUN).
2: Re-hold action ON (hold and re-hold actions)
• Validate the hold action when the power is
turned on.
• Validate the hold action when transferred
from STOP (control STOP) to RUN (control
RUN).
• Validate the re-hold action when the Set
value (SV) is changed.
However, if the Setting change rate limiter
is set to any function other than “0 (0.0)” or
in the remote mode, the re-hold action
becomes invalid.
Re-hold action is only available for deviation
high, deviation low, and deviation high/low.
0
If the Event type is specified
by the initial setting code
when ordering, the factory
set value of Event 1 to 4 hold
action differs depending on
the Event type.
Continued on the next page.
EHo1
EHo2
EHo3
EHo4