User Manual Roth EnergyLogic Touchline/Wireless
Design and function
24 P100011294 E
Push buttons
Push buttons Description
System Combining several (up to 5) wireless connection modules into
a system.
Master Define a wireless connection module as master in a system
with multiple wireless connection modules. Each system must
have one master. As factory settings, the wireless connection
modules are configured as slaves.
See also page 56, chapter 7.1.6.
Zone Combining several wireless connection module channels into
a zone or configuring the internal system grid repeater func-
tion. Up to three zones are possible.
Channels
● Address wireless room thermostat and wireless connec-
tion module.
● Delete addressing.
Table 4: Push buttons wireless connection module
LEDs
LEDs Description
Fuse:
Red LED
● On: The internal fuse has tripped. Page 100, chapter
11.1.
System:
Yellow LED
● On: A wireless connection between up to five wireless
connection modules has been established.
● Double blinking: The internal system grid repeater function
temporarily supports combination of several wireless con-
nection modules into a system.
Master:
Green LED
● On: Wireless connection module is configured as master.
● Off: Wireless connection module is configured as slave.
● Blinking Internal system grid repeater function active.
Zone,
LED Power
(blinking simulta-
neously)
● Blue (Cool):
● Red (% rH):
● Yellow (NO):
Zone 1
Zone 2
Zone 3
Pump:
Green LED
● On: Pump on
● Off: Pump off
C/O Out:
Green LED
The function of the LED "C/O Out" is depending on the set-
tings of parameters P-51. See also parameter description,
page 92.
● Function "Burner" active: On: heating demand
● Function "C/O" active: On: cooling demand
Power:
Green LED
● On: Power supply on
● Off: Power supply off