63
Address Point ID Description Options/Range Units Type R/W Notes
+32 Action #1: Action type F14 UINT16 R/W
+33 Action #1: Action target F14 UINT16 R/W
+34 Action #2: Action type F14 UINT16 R/W
+35 Action #2: Action target F14 UINT16 R/W
+36 Action #3: Action type F14 UINT16 R/W
+37 Action #3: Action target F14 UINT16 R/W
+38 Action #4: Action type F14 UINT16 R/W
+39 Action #4: Action target F14 UINT16 R/W
+40 Not used 0 UINT16 R/W
+41 Operate delay 0-9999
×0.1 sec
UINT16 R/W
+42 Release delay 0-9999
×0.1 sec
UINT16 R/W
+43 Not used 0 UINT16 R/W
352-395 Setpoint #1
396-439 Setpoint #2
440-483 Setpoint #3
484-527 Setpoint #4
528-571 Setpoint #5
572-615 Setpoint #6
616-659 Setpoint #7
660-703 Setpoint #8
704-747 Setpoint #9
748-791 Setpoint #10
792-835 Setpoint #11
836-879 Setpoint #12
880-923 Setpoint #13
924-967 Setpoint #14
968-1011 Setpoint #15
1012-1055 Setpoint #16
Pulse Counters Setup
2940-2947
+0 Source digital input ID 0=not assigned, 1-4=DI1-DI4 UINT16 R/W
+1 Multiplier 0-9999 UINT16 R/W
2940-2941 Counter #1 Setup
2942-2943 Counter #2 Setup
2944-2945 Counter #3 Setup
2946-2947 Counter #4 Setup
Transformer Correction Setup
47072-47099
+0 Ratio correction factor 900-1100
×0.001
UINT16 R/W
+1 Phase angle error -600 to 600 min INT16 R/W
+2, 3 Reserved INT16 R/W
47072-47075 V1 transformer correction
47076-47079 V2 transformer correction