EasyManua.ls Logo

SBC PCD2.M5 Series - Input;Output (I;O) Modules; Module Overview

SBC PCD2.M5 Series
244 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Overview
Input/output (I/O) modules
6-1
6
6 Input/output (I/O) modules
6.1 Module overview
The summary below shows the available digital and analogue I/O modules, counters
etc. for the PCD2 series:
Type Des-
igna-
tion
No. I/
Os or
mods.
Description Input/
output
signal
range
Page
Digital input modules
PCD2.E110 8 I 8 8 inputs 8 ms 24 VDC 6-7
PCD2.E111 8 I 8 8 inputs 0.2 ms 24 VDC 6-7
PCD2.E112 8 I 8 8 inputs 9 ms 12 VDC 6-7
PCD2.E116 8 I 8 8 inputs 0.2 ms 5 VDC 6-7
PCD2.E160 16 I 16 16 inputs 8 ms, connection via 34-pole ribbon
connector
24 VDC 6-9
PCD2.E161 16 I 16 16 inputs 0.2 ms, connection via 34-pole rib-
bon connector
24 VDC 6-9
PCD2.E165 16 I 16 16 inputs 8 ms,
spring terminal connection
24 VDC 6-12
PCD2.E166 16 I 16 16 inputs 0.2 ms,
spring terminal connection
24 VDC 6-12
Digital input modules, electrically isolated
1
)
PCD2.E500 6 I 6 6 inputs
110 … 240 VAC
6-15
PCD2.E610 8 I 8 8 inputs 10 ms, electrically isolated 24 VDC 6-17
PCD2.E611 8 I 8 8 inputs 0.2 ms, electrically isolated 24 VDC 6-17
PCD2.E613 8 I 8 8 inputs 9 ms, electrically isolated 48 VDC 6-17
PCD2.E616 8 I 8 8 inputs 0.2 ms, electrically isolated 5 VDC 6-17
Digital output modules
PCD2.A300 6 O 6 6 outputs 2 A 10 … 32 VDC 6-20
PCD2.A400 8 O 8 8 outputs 0.5 A 5 … 32 VDC 6-22
PCD2.A460 16 O 16 16 outputs 0.5 A, connection via 34-pole rib-
bon connector
10 … 32 VDC 6-24
PCD2.A465 16 O 16 16 outputs 0.5 A, spring
terminal connection
10 … 32 VDC 6-27
Digital output modules, electrically isolated
PCD2.A200 4 O 4 4 make contacts 2 A 250 VAC
50 VDC
6-30
PCD2.A210 4 O 4 4 break contacts 2 A 250 VAC
50 VDC
6-32
PCD2.A220 6 O 6 6 make contacts 2 A 250 VAC
50 VDC
6-34
PCD2.A250 8 O 8 8 make contacts 2 A 48 VAC
505-8 VDC
6-36
PCD2.A410 8 O 8 8 outputs 0.5 A, electrically isolated
1
) 5… 32 VDC 6-38
1)galvanicseparationofoutputstoPCD,channelsthemselvesnotseparated

Table of Contents

Related product manuals