Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Mounting
PCD2.M5_ Classic CPUs and expansion housings
3-21
3
3.5.4 Removeupperpartofhousing
Toinstall(neworreplacement)communicationsinterfaces,theupperpartofthe
housing has to be removed.
● Disconnectallcables(USB,Ethernet,Probus,RS-232).
● Removehousingcover(seeSection3.5.2Removingthehousingcover)
● Pulloutplug-inscrewterminalblocks(X3…X6)
● UnscrewthetwoTORXPlus10IPbolts(forthepositionofthetwobolts,see
below)
● Removeupperpartofhousing
Torx 10 Torx 10
Optional communication interfaces
To simplify customer installation, optional communication interfaces should be
orderedtogetherwiththePCD2.M5_.UptotwoPCD7.F1xxunitscanbepluggedinto
Slots A#1 and A#2.
ThefollowingPCD7.F1xxcommunicationmodulescanbepluggedintoSlotsA#1and
A#2:
A#1
A#2
X4-Port 1
1. PCD7.F1xx
X3-Port 2
2. PCD7.F1xx
PCD7.F110
PCD7.F121
(PCD7.F120mustnotbeused)
PCD7.F130
PCD7.F150
PCD7.F180