Changing the battery on the PCD2.M5xx0
Maintenance
9-1
9
9 Maintenance
PCD2 components are maintenance-free, apart from the CPUs, where the battery
needs to be changed occasionally.
PCD2 components do not contain any parts that can be swapped out by the user. If
hardware problems arise, the components should be returned to SBC.
9.1 ChangingthebatteryonthePCD2.M5xx0
Theresources(registers,ags,timers,countersetc),andpossiblytheuserprogram
and the text strings/DBs, are stored in RAM. To ensure that they are not lost and that
thehardwareclock(wherepresent)continuestorunwhenthereisapowerfailure,
thePCD2sareequippedwithabuffercapacitor(SuperCap)orabufferbattery:
CPU type Buffer Buffer time
PCD2.M5xx0 Renata CR 2032 lithium battery 1-3 years
1)
1)Dependingontheambienttemperature;thehigherthetemperature,theshorterthebuffertime
With new controllers, the batteries are packaged with the units, and have to be
inserted on commissioning. Observe the polarity of the batteries:
Insert CR 2032 coin cells in such a way that the Plus pole is visible
CPUs with lithium batteries are not maintenance-free. The battery voltage is
monitoredbytheCPU.TheBATTLEDlightsupandXOB2iscalledif
the battery voltage is less than 2.4 V
the battery is missing
We recommend changing the batteries with the PCD attached to the power supply, to
avoid any loss of data.