EasyManua.ls Logo

SBC PCD2.M5 Series - PCD2.E500, 6 Digital Inputs for 115 - 230 VAC

SBC PCD2.M5 Series
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Digital input modules, electrically isolated
Input/output (I/O) modules
6-15
6
6.3.1 PCD2.E500,6digitalinputsfor115-230VAC
Application
Module with 6 electrically isolated inputs for alternating current. The inputs are set up
for source operation and have one common "COM" terminal. Only the positive half-
wave of the alternating current is used.
Technical data
Number of inputs 6 electrically isolated from the CPU,
source operation, all inputs to the module in the
same phase
Input voltage 115/230 V 50/60 Hz, sinusoidal
(80to250VAC)
Input current 115 VAC: 5 … 6mA(wattlesscurrent)
230 VAC: 10 … 12mA(wattlesscurrent)
Input delay
switch-on:
switch-off:
typ.10ms;max.20ms
typ.20ms;max.30ms
LED supplied directly from input current
Resistance to interference acc. to
IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling
(wholetrunkgroup)
Electrical isolation voltage 2,000 VAC, 1 min.
Electrical isolation resistance 100 MOhm / 500 VDC
Optocoupler isolation voltage 2.5 kV
Electrical isolation of outputs to the PCD.
The channels are not isolated from each other
Internal current consumption:
(from+5Vbus)
< 1 mA
Internal current consumption:
(fromV+bus)
0 mA
External current consumption:
Terminals: Pluggable10-polescrewterminalblock(440548470),
for wires up to 1.5 mm²
Switch on/off level:
1
0
250 V
AC
80 V
AC
40 V
AC
0 V
AC