Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Digital input modules, electrically isolated
Input/output (I/O) modules
6-15
6
6.3.1 PCD2.E500,6digitalinputsfor115-230VAC
Application
Module with 6 electrically isolated inputs for alternating current. The inputs are set up
for source operation and have one common "COM" terminal. Only the positive half-
wave of the alternating current is used.
Technical data
Number of inputs 6 electrically isolated from the CPU,
source operation, all inputs to the module in the
same phase
Input voltage 115/230 V 50/60 Hz, sinusoidal
(80to250VAC)
Input current 115 VAC: 5 … 6mA(wattlesscurrent)
230 VAC: 10 … 12mA(wattlesscurrent)
Input delay
switch-on:
switch-off:
typ.10ms;max.20ms
typ.20ms;max.30ms
LED supplied directly from input current
Resistance to interference acc. to
IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling
(wholetrunkgroup)
Electrical isolation voltage 2,000 VAC, 1 min.
Electrical isolation resistance 100 MOhm / 500 VDC
Optocoupler isolation voltage 2.5 kV
Electrical isolation of outputs to the PCD.
The channels are not isolated from each other
Internal current consumption:
(from+5Vbus)
< 1 mA
Internal current consumption:
(fromV+bus)
0 mA
External current consumption:
Terminals: Pluggable10-polescrewterminalblock(440548470),
for wires up to 1.5 mm²
Switch on/off level:
1
0
250 V
AC
80 V
AC
40 V
AC
0 V
AC