Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Analogue output modules
Input/output (I/O) modules
6-70
6
6.10.2 PCD2.W6x0,analogueoutputs,4channels,12bitresolution
Application
High-speed output module for general use with 4 channels, each with 12 bit
resolution. Variants for voltage 0 … +10 V, -10 V … +10 V, current 0 … 20 mA.
Module overview
PCD2.W600: Unipolar voltage outputs 0 … 10 V
PCD2.W610: Bipolar voltage outputs -10 V … +10 V, switchable
to unipolar voltage 0 … 10 V / current 0 … 20 mA
Technical data Resolution
Number of output channels: 4,shortcircuitprotected(jumperselectable)
Signal range: W600: 0 … +10 V 2.442 mV
W610: -10 V … +10 V 4,884 mV
0 … +10 V 2,442 mV
with 0..20mA 4,884μA
Galvanic separation: no
Resolution(digitalrepresentation): 12bit(0 … 4095)
Conversion time D/A: typ.10μs
Load impedance Voltage: >3kΩ
Current: <500Ω
Accuracyat25°C(ofoutputvalue) Voltage: ± 0.5 %
Current: ± 0.8 %*)
Temperature error: Voltage: ± 0.1 %(overtemperaturerange
Current: ± 0.2 % 0 … +55 °C)
Internal current consumption:
(from+5Vbus)
W600: max. 4 mA
W610: max. 110 mA
Internal current consumption:
(fromV+bus)
W600: max. 20 mA
W610: 0 mA
External current consumption: max.100mA (typePCD2.W610only,for
currentoutputs)
Terminals: Pluggable10-polescrewterminalblock(440548470),
for wires up to 1.5 mm²
*)Noteoncurrentoutputs:
Since for some applications it is important to be able to reach the outside limit
valuesoftherange(0mA,20mA),currentoutputshavebeenlaidoutaccordingto
the following characteristic line:
During start-up, a voltage of 5 V is sent to all outputs of the W600 module. The
start-up phase lasts 40 ms, then 0 V is sent to the outputs.