Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Digital input modules, electrically isolated
Input/output (I/O) modules
6-17
6
6.3.2 PCD3.E61x,8digitalinputs,electricallyisolated
Application
Input module for source or sink operation with 8 inputs, electrically isolated by
optocoupler. Suitable for most electronic and electromechanical switching elements
at 24 VDC. The PCD2.E611 differs from the PCD2.E610 in its shorter input delay,
typically 0.2 ms.
Technical data
Number of inputs: 8 electrically isolated by optocoupler,
source or sink operation,
all inputs to the model in the same phase
Input voltage E610:
E611:
E613:
E616:
24 VDC(15…30 VDC)smoothed or pulsed
24 VDC(15…30 VDC)smoothed max. 10 % residual ripple
48 VDC (30…60 VDC)smoothed max. 10 % residual ripple
5 VDC (7.5…15 VDC)smoothed max. 10 % residual ripple
Supply voltage:
for source operation:
for sink operation:
E610: E611: E613: E616:
min. 15 V 15 V 30 V 3 V
min. 18 V 18 V 36 V 3.6 V
Input current:
(atinputvoltage)
for source operation:
for sink operation:
E610: E611: E613: E616:
(24VDC) (24VDC) (48VDC) (5VDC)
5 mA 5 mA 2 mA 8.4 mA
3.7 mA 3.7 mA 1.5 mA 6.2mA
Inputdelay(0-1/1-0): E610: E611: E613: E616:
incl. 10 ms 0.2 ms 9 ms 0.2 ms
excl. 10 ms 1.0 ms 9 ms 1.0 ms
Resistance to interference:
acc. to IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling
(wholetrunkgroup)
Electrical isolation voltage:
Optocoupler isolation voltage:
1000 VAC, 1 min.
2.5 kV
Electrical isolation of outputs to the PCD.
The channels are not isolated from each other
Internal current consumption:
(from+5Vbus)
1 … 24 mA
typ. 12 mA
Internal current consumption:
(fromV+bus)
0 mA
External current consumption: max.40mA(allinputs=1)at24VDC,(sourceoperation),
max.18mA(sinkoperation)
Terminals: Pluggable 10-pole spring terminal block
(440548470),forwiresupto1.5mm²