Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Digital combined input/output modules
Input/output (I/O) modules
6-41
6
6.6.1 PCD2.B100,2inputs+2outputs+4digitalinputs/outputs(selectable)
Application
Economical combined input/output module with:
● 2inputs24 VDC/8 ms for source operation, electrically connected
● 2transistoroutputs0.5A/5 … 32 VDC, electrically connected, not short-circuit-
protected, and
● 4combinedI/Os24 VDC/ 8 ms or 0.5 A/5 … 32 VDC on shared I/O terminals.
Technical data on inputs
Number of inputs: 6(2+4), electricallyconnected,
source operation
Input voltage: 24 VDC smoothed or pulsed
2 inputs E0 and E1
low-range:
high range:
-30 … +5 V
+15 … +32 V
4 inputs E/A2...E/A5
low-range:
high range:
-0.5 … +5V*)
+15 … +32 V
All 6 inputs:
low-high switching threshold:
Switching threshold 1-0:
Hysteresis:
Inputcurrent(at24VDC):
Switchingdelay0-1(at24VDC):
Switchingdelay1-0(at24VDC):
13 V typically
6 V typically
7 V typically
7 mA typically
8 ms typically
8 ms typically
*)Negativevoltageisrestrictedbytheprotectivediode(I
max
=0.5A)
Technical data on outputs
Number of outputs: 6(2+4) electricallyconnected,
source operation
not short-circuit-protected
Current: 5...500 mA steady load
Voltage range: 5 … 32 VDC*)
Voltage drop: < 0.3 V at 500 mA for O6 and O7
< 0.7 V at 500 mA for I/O2...I/O5
Total current per module: 3 A steady load
Switch-on delay: typically 10 µs
Switch-off delay: 50μstypically(100μsmax.),(ohmicload5..500mA),
longer for inductive load because of protective diode.
*) If the state of a combined output is to be read off,
voltage U
ext
must be at least 17 VDC, as the state and the LED are displayed via the
input.