EasyManua.ls Logo

SBC PCD2.M5 Series - PGU Connection (PORT # 0) (RS-232) as Communication Interface

SBC PCD2.M5 Series
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG Communication interfaces
5
5-4
Onboard interfaces
5.3.2 PGU connection (PORT # 0) (RS-232) as communication interface
When commissioning/programming are complete, the port can be used for other
purposes.
Option 1: Congurationwithdesiredprotocol
(S-BusPGUconguration)
Option 2: Assignment(SASI)intheuserprogram
(theportmustnotbeconguredasanS-BusPGUport)
■ Ifanotherprogrammingdeviceisconnectedduringoperation
instead of the peripheral device, the unit will switch over
automaticallytoPGUmode(pin6logical"1"(DSR);inPGU
mode:DSRPING=“1”).
■ Beforeusingtheporttoconnectanotherperipheraldevice,Port
0mustbereconguredbymeansofanSASIinstruction.
2
1
4
3
6
5
8
7
9
GND SGN
TX
RX
RTS
1)
CTS
1)
CTS
RTS
TXD
RXD
DCD PGD
PGU-Plug
D-SUB 9 pol.
(female)
PeripheralCable
+5V
(
just for PGU)
1)
When communicating with terminals, check whether some connections are
equipped with bridges or need to be set with the "SOCL" command to "1" or "0". It
isgenerallyrecommendedtouseahandshake(RTS / CTS).

Table of Contents