EasyManua.ls Logo

SBC PCD2.M5 Series - MP-Bus with PCD7.F180, Port#1 & Port#2

SBC PCD2.M5 Series
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG Communication interfaces
5
5-15
Serial interfaces - Slots A1 and A2
5.4.5 MP-BuswithPCD7.F180,Port#1&Port#2
PCD7.F180:
Connection module to MP-Bus
The user can connect an MP-Bus line with 8 drives and sensors.
Connections
PCD7.F180
PCD7.F180
10
11
12
13
14
15
16
17
18
19
0
1
2
3
4
5
6
7
8
9
11, (1) MP
12, (2) ,MFT’
13, (3) ,IN’
14, (4) GND
10, (0) -
15, (5) -
1, (1) MP
2, (2) ,MFT’
3, (3) ,IN’
4, (4) GND
0, (0) -
5, (5) -
Socket A1
Socket A2
x3, Port 2
x4, Port 1
MP-Bus signal line (18V in/out)
MFT-Parametrie device (MP-Bus intern)
MFT-Parametrie device detection (Input 10 kOhm, Z5V1)
Ground connection MFT-Parametrie device
GND (A-)
GND
MP-Bus signal line (18V in/out)
MFT-Parametrie device (MP-Bus intern)
MFT-Parametrie device detection (Input 10 kOhm, Z5V1)
Ground connection MFT-Parametrie device
GND (A-)
GND
There are the following parameterization devices of BELIMO
®
:
ManualControlUnit MFT-H Withitsownpowersupply/batteries
PC-Tool MFT-P WiththeadapterZIP-RS-232
Supply option
Common supply for control and drive
+
11
PCD2
13
10
18
19
14
15
16
17
-
/D
D
+
WD
-
-
+
+
12
L
N
L N
±20%
drives MFT Parametrie device
Port #1
Controller
24 VDC

Table of Contents

Related product manuals