EasyManua.ls Logo

SBC PCD2.M5 Series - Power Supply, Earthing Scheme, Cable Layout; External Power Supply

SBC PCD2.M5 Series
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Power supply, earthing scheme, cable layout
PCD2.M5_ Classic CPUs and expansion housings
3-24
3
3.7 Powersupply,earthingscheme,cablelayout
3.7.1 External power supply
Simple, small installations
+18V
0V
GND
L N
19VAC
±15%
Trafo min. 50VA
Sensors: Electro-mechanical switches
Actuators: Relays, lamps, small valves with < 0.5A switching current
Suitable for PCD2.Mxxxx
Modules: PCD2.E1xx, E5xx, E6xx, A2xx, A4xx, B1xx, G4xx
PCD2.W1xx, W2xx, W3xx, W4xx, W5xx, W6xx
Small to medium installations
+18V
0V
GND
+24V =
0V
L
N
L
N
19VAC
±15%
Trafo min. 50VA
24VDC
±20%
Control
Sensors: Electro-mechanical and proximity switches, photoelectric
barriers
Actuators: Relays, lamps, displays, small valves with < 0.5A switching
current
Suitable for PCD2.Mxxxx
Modules PCD2. E1xx, E5xx, E6xx, A2xx, A4xx, B1xx, G4xx
PCD2.W1xx, W2xx, W3xx, W4xx, W5xx, W6xx
PCD2. H1xx
*)
, H2xx
*)
, H3xx
*)
PCD7.D2xx
*)
*)Thesemodulesmustbeconnectedtoasmoothed24VDCsupply

Table of Contents