Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
General technical details
PCD2.M5_ Classic CPUs and expansion housings
3-4
3
Noise immunity acc. to EN61000-6-4
Mechanism and mounting
Housing material Base:
Cover:
Fibreoptics: PC,crystal-clear
Mounting rail 2top-hatrailsacc.toEN50022-35(2x35mm)
Connections
Terminal
blocks
Spring
terminals
10-pole,
4-pole
Spring
terminals
10-pole
Spring
terminals
14-pole,
12-pole,
8-pole
Spring
terminals
24-pole,
6-pole
Earth
terminal
Terminal
2-pole
supply
Section
stranded
single wire
0.5..2.5 mm²
0.5..2.5 mm²
0.5..2.5 mm²
0.5..2.5 mm²
0.5...1.5 mm²
0.5...1.5 mm²
0.5...1.0 mm²
0.5...1.0 mm²
0.08...
2.5 mm²
0.5...
1.5 mm²
The terminal blocks may only be plugged onto 20 times. They must then be replaced, to
guarantee a reliable contact
Length of
insulation
7 mm 7 mm 7 mm 7 mm 5...6 mm 7 mm
Standards / approvals
EN/IEC EN/IEC61131-2“Programmablecontrollers”
Shipbuilding ABS, BV, DNV, GL, LRS, PRS.
Please verify if your chosen product is mentioned in the
list of corresponding Type-Approval-Company under
www.saia-support.com.
cULus-listed Please verify if your chosen product is listed in the corresponding
Certicateunderwww.saia-support.com. The condition for cULus
Compliance are mentioned on the sheet annexed to the product
or can be required under www.saia-support.com.

Table of Contents

Related product manuals